<?xml version="1.0" encoding="utf-8"?>
<Spec id="325" path="\c\0\c00f686bb1fca8dcafa1c4251cae609f.pdf"><Text id="55866" page="5">This document and its content, is for authorized company use only</Text><Text id="55867" page="5">1.1 Objective The specification establishes requirements for design, construction and testing of high voltage transformers for onshore and offshore service.</Text><Text id="55868" page="5">The specification contains three parts. Section 2 is valid for all transformers, section 3 is applicable to liquid-immersed transformers, and section 4 is applicable for dry insulated transformers.</Text><Text id="55869" page="5">The referred standards are either based on IEC or based on IEEE. The standards have been referred to by one common number as shown in section 5.3. The IEEE standards are applicable in US or Canada, while IEC standards are applicable elsewhere.</Text><Text id="55870" page="5">The specification is based on IEC 60076 or IEEE C57 whichever are applicable, and the content specifies:</Text><Text id="55871" page="5">In more detail specific IEC / IEEE requirements. Which one of several optional IEC / IEEE alternatives to be used. Requirements not covered in IEC / IEEE. Alternative requirements to be used instead of requirements described in IEC / IEEE.</Text><Text id="55872" page="5">The specification can be used for low voltage transformers, such as 690 - 400 V transformers. The document can be used as basis for</Text><Text id="55873" page="5">Subsea transformers, however requirements related to subsea environment are not part of this document. Generator step-up transformers to connect wind turbines to a network. These transformers are installed in the nacelle or in the tower or outside close to the wind turbine. Ref IEC 60076-16. Currently there is no comparable IEEE standard on this topic.</Text><Text id="55875" page="6">In this document the IEC terminology is used for Earth instead of the ANSI terminology which is Ground.</Text><Text id="55876" page="6">1.2 Target group The target group for this document is personnel involved in preparing technical and operational requirements and standards to be applied in project development work.</Text><Text id="55877" page="6">1.3 Provision Provision is made in Management System (TR3020 Electrical, Technical Requirements and Standards).</Text><Text id="55878" page="6">2.1 General SR-47880 - Design of transformers shall be in accordance with:</Text><Text id="55879" page="7">Requirements: Transformers Classification: Internal Project development, Requirements, TR3123, Version 3.02 Page 7 of 24 Printed: 15/05/2023 14:42:48</Text><Text id="55880" page="8">2.2 Duty and rating SR-47882 - All tappings shall be full-power tappings.</Text><Text id="55881" page="8">SR-47883 - Harmonic currents in e.g. converter transformers will increase losses and temperatures of the windings and nearby steel parts of the transformer. The effect of harmonic currents shall be taken into account according to IEC 61378-1 or IEEE C57.18.10 respectively.</Text><Text id="55882" page="8">SR-47884 - Ancillary components and construction features such as bushings, cable-end connections, tap-changing devices, internal leads, liquid expansion space etc., shall be dimensioned in a manner that will not limit the loading to less than the capability of the windings.</Text><Text id="55883" page="8">2.3 Windings SR-47886 - For transformers rated above 16 MVA all tapped windings shall be separate windings. This means that there shall not be tappings made as an integrated part of a winding.</Text><Text id="55884" page="8">SR-47887 - One of the windings shall be delta connected. For a stabilizing winding both ends of at least one corner of the delta shall be brought out on separate bushings.</Text><Text id="55885" page="8">SR-47888 - For transformers with specifications based on IEC: The insulation level for low voltage transformers shall be according to U m ≤ 1.1 kV given by table 3 in section 12.1 in IEC 60076-11.</Text><Text id="55886" page="8">SR-47889 - Increased losses due to harmonic currents shall be taken into account in thermal dimensioning in accordance with IEC 61378-1 or IEEE C57.18.10 respectively.</Text><Text id="55887" page="8">2.4 Neutral points SR-47891 - Neutral point(s) shall have uniform insulation if not otherwise stated in the datasheet. The transformer shall be designed for operation with neutral points directly earthed, earthed via a resistor or reactor, or isolated. The neutral point(s) shall be brought out on a separate bushing.</Text><Text id="55888" page="8">SR-47892 - The rated current of the neutral point shall be equal to the rated current of the corresponding transformer windings terminals.</Text><Text id="55889" page="8">SR-47893 - Where a Neutral Earth Resistor (NER) is specified in datasheet, then the resistor shall be connected between the neutral point and the earth bar. A current transformer shall be</Text><Text id="55890" page="9">SR-47903 - All signals from instruments, Current Transformers CTs, sensors etc. shall be connected in a separate cabinet. Internal wiring shall be according to TR3120 section 4.10.</Text><Text id="55891" page="9">provided for measuring the neutral point current. The current transformer and the NER shall be mounted in a separate purpose made enclosure mounted outside of the transformer housing.</Text><Text id="55892" page="9">SR-47904 - Light fixture and space heaters inside cabinets shall be according to TR3120 section 4.17.</Text><Text id="55893" page="9">SR-47894 - The CT shall be according to IEC 61869-2 or IEEE C57.13 respectively. All secondary leads shall be brought out to terminal blocks in the cabinet. The terminals shall be provided with short-circuiting links.</Text><Text id="55894" page="9">SR-47895 - The cable for connection of the NER to the transformer neutral point must be dimensioned for overvoltages due to e.g. failures in other part of the network.</Text><Text id="55895" page="9">2.5 Core SR-47897 - All metal parts of the core, frame, tank etc. shall be bonded to earth.</Text><Text id="55896" page="9">SR-47898 - The core sheets of the magnetic circuit of transformers exceeding 16 MVA shall be bonded to the core clamping structure through at least one removable core-insulation test link. The link shall be placed in an accessible position. With the bond removed, the core sheets of the magnetic circuit shall be insulated from the core clamping and all structural parts.</Text><Text id="55897" page="9">2.6 Noise SR-47900 - If not otherwise is specified in the datasheet at then the sound pressure level when the transformer is energised, plus when cooling equipment and any oil-circulating pumps are in service, shall not exceed 85 dB(A) at 1m distance measured according to IEC 60076-10 or IEEE C57.12.90 and IEEE C57.12.91 respectively.</Text><Text id="55898" page="9">2.7 Terminals and wiring SR-47902 - Marking of internal components and wiring shall be according to TR3120 section 4.11.</Text><Text id="55899" page="9">SR-47905 - Earthing of the transformer shall be according to TR3120 section 4.8 (high voltage equipment).</Text><Text id="55900" page="9">SR-47906 - The transformer shall be provided with a minimum of two earth terminals for connection to the external earth grid. The terminals shall be located on opposite sides of the</Text><Text id="55901" page="10">2.9 Carriage SR-47912 - Transformers shall be provided with lifting lugs to enable lifting of the complete unit.</Text><Text id="55902" page="10">2.10 Surface treatment SR-47914 - Surface and protective coating for transformers located outdoor in natural ventilated area shall be according to TR0042 cl 2. The manufacturer’s standard painting system and standard colour are acceptable for transformers located in a mechanically ventilated area.</Text><Text id="55903" page="10">SR-47915 - Isocyanate-based products (e.g. polyurethanes) or products that release di- isocyanates when heated shall not be used.</Text><Text id="55904" page="10">transformer to enable easy connection to the earth grid. Both terminals shall be boss type to enable connection via lugs.</Text><Text id="55905" page="10">SR-47907 - For transformers with specifications based on IEEE, 2 hole lugs shall be provided.</Text><Text id="55906" page="10">2.8 Labelling SR-47909 - The requirement for labelling is stated in TR3120.</Text><Text id="55907" page="10">SR-47910 - The rating plate shall be in accordance with requirements in :</Text><Text id="55908" page="11">2.11 Vibration damper SR-47917 - Use of vibration dampers shall be evaluated to ensure that transformers do not cause unwanted vibration and noise to their surroundings.</Text><Text id="55909" page="11">2.12 Tolerances SR-47919 - The tolerances shall be according to IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively.</Text><Text id="55910" page="11">SR-47920 - The plus tolerance for the noise level is zero, i.e. the measured noise level shall be equal to or below the stated limit.</Text><Text id="55911" page="11">3.1 General SR-47923 - The transformer shall have IP-rating according to requirements for outdoor or naturally vented area in TR3120 cl 3.1.</Text><Text id="55912" page="11">3.2 Windings See section 2.3 in this document for general requirements.</Text><Text id="55913" page="11">SR-47926 - For transformers based on IEEE specifications the insulation paper of the windings shall be thermally upgraded IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively.</Text><Text id="55914" page="11">See requirements for high temperature design in section 3.5.3.</Text><Text id="55915" page="11">SR-47928 - The rated withstand voltages for transformer windings shall be selected to the highest value as given in table 2 in IEC 60076-3. Values indicated with “note a” in table 2 in IEC 60076-3 shall not be used.</Text><Text id="55916" page="12">3.3 Insulating liquid SR-47930 - Mineral inhibited oil according to IEC 60296 or IEEE C57.106 shall be used for transformers with U m equal to or above 72,5 kV or 69 kV for IEC or IEEE based specifications, respectively. SR-47931 - Silicone type oil can be used for transformers with U m equal to or below 36 kV or 34,5 kV for IEC or IEEE based specifications.</Text><Text id="55917" page="12">SR-47932 - Silicone type oil shall not be used for transformers with On-Load Tap Changer, OLTC, due to the poor lubrication of the tap contacts.</Text><Text id="55918" page="12">SR-47933 - Use of insulation liquids for allowing temperatures above 105°C, e.g. listed in /9/, shall not be used for transformers with U m equal to or above 72,5 kV or 69 kV for IEC or IEEE based specifications due to the limited experience of dielectric withstand capability of such insulating liquids.</Text><Text id="55919" page="12">3.4.1 On-load tap changer, OLTC SR-47936 - If an OLTC is specified, then the following shall apply:</Text><Text id="55920" page="12">The OLTC and the corresponding motor drive cabinet shall be in accordance with IEC 60214-1 or IEEE C57.131 respectively. A protective device shall be installed to detect sudden pressure increase in the diverter switch oil compartment. Light fixture and space heaters inside cabinet shall be according to TR3120 section 4.17. Manholes shall be provided for accessing the contacts of the OLTC during servicing.</Text><Text id="55921" page="13">3.4.2 Off-circuit tap changer, OCTC SR-47938 - If an OCTC is specified, then the following shall apply:</Text><Text id="55922" page="13">The OCTC and the corresponding motor drive cabinet shall be in accordance with IEC 60214-1 or IEEE C57.131 respectively. The number of positions shall be 5 unless otherwise agreed. There shall be a locking device at the manual drive mechanism which requires a deliberate act by the operator to remove it before operating the drive. The manual drive mechanism shall be capable of being locked in any one of the tap positions. If a motor drive is specified, then the light fixture and space heaters inside cabinet shall be according to TR3120 section 4.17.</Text><Text id="55924" page="13">3.5.1 General The external cooling medium is either air or water.</Text><Text id="55925" page="13">SR-47942 - The yearly average ambient cooling medium temperature is stated in the datasheet. Otherwise the yearly average temperature shall be as stated in IEC 60076-2 or IEEE C57.12.00 respectively.</Text><Text id="55926" page="13">SR-47943 - In case of water cooling, the coolers shall be of double wall design, and shall be equipped with a leakage monitoring system. All water exposed materials in the cooler shall be compatible with the cooling water.</Text><Text id="55927" page="13">SR-47944 - Plate and Frame Heat Exchangers shall be according to cl 2 in TR0041. The flanges for the water side of the heat exchanger shall be according to cl 2 in TR2000.</Text><Text id="55928" page="13">3.5.2 Conventional paper – oil insulation The stated yearly average temperature of the external cooling medium is 20 °C for IEC and 30 °C for IEEE based specifications.</Text><Text id="55929" page="13">SR-47947 - The average temperature rise of the transformer windings at rated power shall not exceed 65 K, and the top oil temperature shall not exceed 60 K. Reference is made to IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively.</Text><Text id="55930" page="13">SR-47948 - If the yearly average temperature of the external cooling medium given by the</Text><Text id="55931" page="14">Table 1: Allowed temperature rises of average windings and top oil</Text><Text id="55932" page="14">datasheet exceeds the stated yearly average temperature from the standards (IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively), then the average temperature rise limit of the transformer windings and top oil shall be reduced by the same amount as the excess. Three examples are given for yearly average external cooling medium excess temperatures of 0 K, 10 K and 20 K respectively.</Text><Text id="55933" page="14">3.5.3 High temperature insulation High temperature insulation design is based on temperatures in excess of thermal class 105 °C, for the solid insulation, see reference IEC 60076-14 or IEEE 1276 respectively.</Text><Text id="55934" page="14">SR-47952 - The high temperature design shall as a minimum be based on hybrid insulation system. The average temperature rise of the transformer windings at rated power shall not exceed 95 K, and the top oil temperature shall not exceed 60 K. Reference to other requirements in IEC 60076-14 or IEEE 1276 respectively..</Text><Text id="55935" page="14">SR-47953 - Minimum thermal class for the high-temperature solid insulation shall be 155 °C.</Text><Text id="55936" page="14">SR-47954 - If the yearly average temperature of the external cooling medium from the datasheet exceeds the stated yearly average temperature from the standards (IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively), then the average temperature rise limit of the transformer windings and top oil shall be reduced by the same amount as the excess.</Text><Text id="55937" page="14">3.6 Bushings Type of bushings will be described in datasheet.</Text><Text id="55938" page="14">SR-47957 - For air insulated bushings the IP code of the protective housing for cable terminations shall be according to section 3.1, if not otherwise stated.</Text><Text id="55939" page="14">SR-47958 - For plug-in type bushing or equivalent touch proof solution, a portable earthing device shall be delivered, if not otherwise stated.</Text><Text id="55940" page="14">SR-47959 - It shall be provision for measuring voltage at the bushing to be able to check if the</Text><Text id="55941" page="15">SR-47960 - The transformer bushings shall be of outdoor type, and shall comply with IEC 60137 or IEEE C57.19.00 respectively..</Text><Text id="55942" page="15">3.7 Current transformers SR-47962 - The CT shall be according to IEC 61869-2 or IEEE C57.13 respectively..</Text><Text id="55943" page="15">3.8 Tank See requirements in section 2.9. SR-47965 - The transformer tank shall be designed for a static overpressure of at least 1 barg.</Text><Text id="55944" page="15">SR-47966 - The transformer skid base shall be designed for handling of the liquid filled transformer.</Text><Text id="55945" page="15">SR-47967 - Jacking pads should be available on the transformer tank to allow jacking of the liquid filled transformer.</Text><Text id="55946" page="15">SR-47968 - There shall be valves provided for at least:</Text><Text id="55947" page="15">Liquid filling, draining and venting of all liquid volumes. Liquid sampling from top of the tank. The valve shall be placed within reach from the floor such that there is no need to use of scaffolding or a ladder for sampling. Isolating external cooling equipment from transformer tank. Isolating each compartment of the conservator tank from the transformer tank.</Text><Text id="55948" page="15">SR-47969 - A moisture-removing breather shall be provided for each chamber of the oil conservator tank.</Text><Text id="55949" page="15">SR-47970 - Transformers with U m equal to or above 24 kV shall have a diaphragm-type oil preservation system to avoid direct contact between the transformer oil and air. A flexible diaphragm or bladder shall be used for this purpose.</Text><Text id="55950" page="15">SR-47971 - The liquid conservator shall have a separate compartment for the OLTC diverter switch oil if OLTC is part of the transformer. For this compartment a free breathing system can be used.</Text><Text id="55951" page="15">SR-47972 - 316L stainless steel shall be used for fasteners (screws, bolts, nuts, etc.) up to and including a diameter of 10 mm. For diameters above 10 mm fasteners shall be hot dip</Text><Text id="55952" page="16">galvanised in accordance with ASTM A153 or coated with PTFE with anticorrosion pre- treatment such as cermet.</Text><Text id="55953" page="16">The requirement for fasteners does not apply to fasteners inside the transformer tank.</Text><Text id="55954" page="16">3.9 Protective housing for cable terminations SR-47975 - The IP rating for protective housing shall be according to requirements in section 3.1.</Text><Text id="55955" page="16">SR-47976 - It shall be possible to measure voltage at the terminals before removal of the protective housing of the cable terminals.</Text><Text id="55956" page="16">3.10 Control and monitoring SR-47978 - The following instrumentations shall be provided as a minimum:</Text><Text id="55957" page="16">Oil level gauges for each compartment of the conservator tank. The gauges shall have contacts for high and low oil level. Gas relay installed in the pipe between transformer tank and conservator. The relay shall have contacts for alarm and trip indicating slow gas development or rapid pressure build up. Hermetically sealed transformers shall be equipped with pressure relief device. The device shall have contact for the trip circuit. Top oil temperature measurement enabling local and remote reading. There shall be two sets of contacts. One for the alarm circuit and one for the trip circuit. Winding temperature indication based on thermal image enabling local and remote reading. There shall be two sets of contacts. One for the alarm circuit and one for the trip circuit. For OLTC pressure increase device (see section 3.4.1), there shall be contact for the trip circuit. In case of OFWF cooling – there shall be a water leakage monitoring system enabling remote indication. In case of Oil Forced, OF, cooling – there shall be an oil flow indicating system enabling remote indication.</Text><Text id="55958" page="17">3.11 Testing SR-47980 - Routine tests shall be in accordance with IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively..</Text><Text id="55959" page="17">SR-47981 - The following non-routine tests listed in IEC 60076-1 or IEEE C57.12.00 and IEEE C57.12.90 respectively shall be performed:</Text><Text id="55960" page="17">Temperature-rise test for transformers rated 16 MVA and above. Determination of capacitances windings-to-earth, and between windings for all converter transformers Audible sound level.</Text><Text id="55961" page="17">SR-47982 - If several identical transformers are ordered, the non-routine test should be performed on one transformer only.</Text><Text id="55962" page="17">SR-47983 - A dissolved gas in oil analysis shall be performed according to IEC 60076-2 or IEEE C57.12.00 respectively.</Text><Text id="55963" page="17">4.1 Windings See section 2.3 in this document for general requirements. SR-47987 - The insulation level shall be according to:</Text><Text id="55964" page="17">List 2 in table 3 of section 12.1 for the IEC-based specification IEC 60076-11. The highest indicated basic lightning impulse level stated in table 5 in section 5.10 for the IEEE based specification IEEE C57.12.01 and IEEE C57.12.91.</Text><Text id="55965" page="17">SR-47988 - The minimum winding insulation class shall be:</Text><Text id="55966" page="17">155°C (insulation class F) for IEC based specifications (IEC 60076-11) 150°C for IEEE based specifications (IEEE C57.12.01 and IEEE C57.12.91).</Text><Text id="55967" page="17">SR-47989 - Corresponding winding hot spot temperature shall be in accordance with IEC 60076-12 or IEEE C57.12.01 respectively.</Text><Text id="55968" page="18">SR-47990 - The windings shall be solid-casted or VPI.</Text><Text id="55969" page="18">SR-47991 - All terminals shall be of copper type. This also applies when aluminium windings is specified.</Text><Text id="55970" page="18">4.2 Tappings SR-47993 - The tapping shall be on the primary windings, with steps of approximately +/- 2 x 2.5% of rated voltage if not specified otherwise.</Text><Text id="55971" page="18">SR-47994 - OCTC tapping selection should be made by the use of bolted links instead of off- circuit tap-changers</Text><Text id="55972" page="18">SR-47995 - If OLTC is specified, then the corresponding motor drive cabinet shall be in accordance with IEC 60214-1 or IEEE C57.131 respectively.</Text><Text id="55973" page="18">4.3 Core SR-47997 - The transformer core shall be dimensioned for continuous operation at 110 % of rated voltage referred to the principal tapping and rated power. This is an additional requirement to IEC 60076-11 or IEEE C57.12.01 and IEEE C57.12.91 respectively.</Text><Text id="55974" page="18">4.4 Cooling and allowed temperature rise SR-47999 - The yearly average ambient cooling air temperature is stated in the datasheet. Otherwise the yearly average temperature shall be as stated in IEC 60076-11 or IEEE C57.12.01 and IEEE C57.12.91 respectively..</Text><Text id="55975" page="18">SR-48000 - The stated yearly average temperature of the external cooling medium is 20 °C for IEC and 30 °C for IEEE based specifications. The corresponding average temperature rise of the transformer windings at rated power shall not exceed 100 K for IEC and 90 K for IEEE based specifications. Reference is made to IEC 60076-11 or IEEE C57.12.01 and IEEE C57.12.91 respectively.</Text><Text id="55976" page="18">SR-48001 - If the yearly average temperature of the external cooling air given by the datasheet exceeds the stated yearly average temperature from the standards IEC 60076-11 or IEEE C57.12.01 and IEEE C57.12.91 respectively, then the average temperature rise limit of the transformer windings shall be reduced by the same amount as the excess.</Text><Text id="56009" page="6">IEC IEEE 2011 IEC 60076-1 Power transformers, Part 1: General 2010 2010 IEEE C57.12.00 IEEE C57.12.90 General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers 2011 2010 IEC 60076-2 Power transformers, Part 2: Temperature rise IEEE C57.12.00 General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers 2013 2010 IEC 60076-3 IEEE C57.12.00 Power transformers, Part 3: Insulation levels, dielectric tests and external clearances in air General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers 2006 2010 IEC 60076-5 IEEE C57.12.00 Power transformers, Part 5: Ability to withstand short circuit General Requirements for Liquid-Immersed Distribution, Power, and Regulating</Text><Text id="56010" page="7">2005 2010 IEC 60076-7 IEEE C57.12.00 Power transformers, Part 7: Loading guide for oil- immersed power transformers General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers 2005 IEC 60076-10 Power transformers, Part 10: Determination of sound levels 2010 2011 IEEE C57.12.90 IEEE C57.12.91 Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers Test Code for Dry-Type Distribution and Power Transformers 2004 IEC 60076-11 Power transformers, Part 11: Dry-type transformers 2005 2011 IEEE C57.12.01 IEEE C57.12.91 General Requirements for Dry- Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings. Test Code for Dry-Type Distribution and Power Transformers 2008 2005 IEC 60076-12 IEEE C57.12.01 Power transformers, Part 12: Loading guide for dry- type power transformers General Requirements for Dry- Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings 2013 IEEE 1276 2000 IEC 60076-14 IEEE Guide for the application of High-Temperature Insulation Materials in Liquid-Immersed Power Transformers Power transformers, Part 14: Design and application of liquid- immersed power transformers using high- temperature insulation materials</Text><Text id="56011" page="10">IEC IEEE 2011 IEC 60076-1 Power transformers, Part 1: General 2010 2010 IEEE C57.12.00 IEEE C57.12.90 General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers 2011 1998 IEC 61378-1 IEEE C57.18.10 Converter Transformers, Part 1: Transformers for industrial applications Practices and Requirements for Semiconductor Power Rectifier Transformers</Text><Text id="56012" page="14">Yearly average excess temperature of external cooling medium Limit for average temperature rise of transformer windings Limit for temperature rise of transformer top oil 0 K 65 K 60 K 10 K 55 K 50 K 20 K 45 K 40 K</Text></Spec>